GDA 3160 R134a Flush Mount Refrigerant Gas Detector, Range: 0-1000 ppm; NDIR Sensor, Output: 4-20 mA, 0-20 mA, 0-5 VDC or 0-10 VDC, Alarm Relay, Power: 24 VDC 3-wire powered, Mute Switch, Buzzer, Factory set alarm: 250 ppm, Factory Calibrated Output set to: 4-20 mA
Detectable Gas Range | 0-1000 ppm |
---|---|
Measuring Units | ppm |
Sensor Technology | Non Dispersive Infra-Red (NDIR), Dual Wavelength |
Sensing Method | Diffusion |
Response Time (τ90) | ~60 sec |
Warm Up Time | < 30 min (full Spec.) |
Resolution | 1-2 ppm |
Span Calibration Gas | 1000 ppm of target gas |
Zero Calibration Gas | Nitrogen |
Functional/Bump Test Gas | 500-1000 ppm |
User Interface Type | Calibration Buttons |
Internal Buzzer | Yes |
Light Colour | LED Red |
Sounder Output | 70 dB @ 1 m |
Recommended Supply Voltage | 24 VDC |
Supply Voltage Range | 12 VDC to 32 VDC |
Outputs | 1 x Analogue, 1 x Digital |
Output Specifications | 0-20 mA, 4-20 mA, 0-5 VDC, 0-10 VDC (4-20 mA Default) |
Analogue Output Specifications | 4-20 mA (500 ohms max load) |
Digital Output Specifications | Alarm 1 |
Dimension | 116 x 76 x 12 mm (L x W x D) (45 mm in wall) |
Weight | 160 g |
Material | ABS Plastic |
Mounting | Flush mount |
Mounting Height | 300-500 mm From Floor |
Operating Temperature | -20 to 40 °C |
Storage Temperature | -20 to 60 °C |
Operating Humidity | 5% to 95% RH (non-condensing) |
Operating Pressure | 800 to 1150 hPa |
IP Rating | IP20 |
Warranty | 12 Months |